Explosion-proof conv. MCP, IP66

761697.1

The manual call point was developed for explosion hazard areas, where gas or dust can cause an explosive atmosphere. The device provides a maximum security, without using a safety barrier. Equipped with preinstalled resistors, the MCP can be used for ESSER Fire Alarm Systems without additional preparation.
  • High IP protection up to IP55
  • Plug-in terminals
  • Standard keys with double function: Open, reset
  • Service key with triple function: Test, open, reset
  • "Out of Order" marking an inoperative detector by turning the enclosed operating front foil

Additional Information:
For detailed information on installation and operation, see documentation part no. 798920. For operation with standard groups ex-barrier item no. 764744 must be used in zone 1 and zone 2!

Scope of Delivery:
1 x glass pane 704960
1 x key 769910
1 x Manual call point housing, red
1 x IP 55 shrink sleeve

Rated voltage
0.5 - 30 V
Rated current
In < 0.1A / Ik < 4.5A
Connection terminals
0.08-2.5 mm²
Type of protection
IP66
Ex protection
II2G Ex emb IIC T6 Gb; II2D Ex tb IIIC T80°C Db
Material
PC-plastic
Dimensions
W: 135 mm H: 135 mm D: 61 mm
Weight
0.5 kg
Operating temperature
-25 … + 60 °C
Storage temperature
-35 … + 60 °C
Type approval
G206113
EX type approval
BVS 09 ATEX E 016 X